16 Endress+Hauser
FOUNDATION Fieldbus
The digital communication signal is transmitted to the bus via a 2-wire connection. The bus also provides the
auxiliary energy. For further information on the network structure and grounding and for further bus system
components such as bus cables, see the relevant documentation, e.g. Operating Instructions BA013S
"FOUNDATION Fieldbus Overview" and the FOUNDATION Fieldbus Guideline.
Cable specifications:
Use a twisted, shielded two-wire cable, preferably cable type A
Note!
For further information on the cable specifications, see Operating Instructions BA013S "FOUNDATION
Fieldbus Overview", FOUNDATION Fieldbus Guideline and IEC 61158-2 (MBP).
Devices with Harting plug Han7D
P01-xMD7xxxx-04-xx-xx-xx-000
Left: electrical connection for devices with Harting plug Han7D
Right: view of the plug connector at the device
Devices with M12 plug
P01-xMD7xxxx-04-xx-xx-xx-008
Left: electrical connection for devices with M12 plug
Right: view of the plug at the device
Endress+Hauser offers for devices with M12 plug the following accessories:
Plug-in jack M 12x1, straight
Material: Body PA; coupling nut CuZn, nickel-plated
Degree of protection (fully locked): IP67
Order number: 52006263
Plug-in jack M 12x1, elbowed
Material: Body PBT/PA; coupling nut GD-Zn, nickel-plated
Degree of protection (fully locked): IP67
Order number: 51006327
Cable 4x0.34 mm
2
with M12 socket, elbowed, screw plug, 5 m length
Material: Body PUR; coupling nut CuSn/Ni; cable PVC
Degree of protection (fully locked): IP67
Order number: 52010285