Deltabar S
Endress+Hauser 25
"Separate housing" version With the "separate housing" version, you are able to mount the housing with the electronics insert at a distance
from the measuring point. This facilitates trouble-free measurement:
• Under particularly difficult measuring conditions (at installation locations that are cramped or difficult to
access)
• If rapid cleaning of the measuring point is required
• If the measuring point is exposed to vibrations.
You can choose between different cable versions:
• PE (2 m, 5 m and 10 m)
• FEP (5 m).
ä 68 ff, Feature 110, "Additional options 2", Version "G".
For the dimensions, see ä 50.
P01-xMD7xxxx-11-xx-xx-en-010
In the case of the "separate housing" version, the sensor is delivered with the process connection and cable ready
mounted. The housing and a mounting bracket are enclosed as separate units. The cable is provided with a socket at both
ends. These sockets are simply connected to the housing and the sensor.
1 Process connection with sensor
2 Cable, both ends are fitted with a socket
3 Mounting bracket provided, suitable for pipe and wall mounting
4 Housing with electronic insert
Degree of protection for the process connection with sensor with the use of
• FEP cable:
– IP 69K
– IP 66 NEMA 4/6P
– IP 68 (1.83 mH
2
O for 24 h) NEMA 4/6P
• PE cable:
– IP 66 NEMA 4/6P
– IP 68 (1.83 mH
2
O for 24 h) NEMA 4/6P
Technical data of the PE and FEP cable:
• Minimum bending radius: 120 mm (4.72 inch)
• Cable extraction force: max. 450 N
• Resistance to UV light
Use in hazardous area:
• Intrinsically safe installations (Ex ia/IS)
• FM/CSA IS: for Div.1 installatin only
➀
➁
➂
➃
r ³ 120 mm
IP xx
(see chapter
“Ordering information”)
FEP cable:
IP 69K
IP 66/68 NEMA 4/6P
PE cable:
IP 66/68 NEMA 4/6P