Deltabar S
Endress+Hauser 9
Explanation of terms
Explanation of the terms: Turn down (TD), set span and zero based span
Case 1:
Lower range value Upper range value
Example:
Lower range value (LRV) = 0 mbar
Upper range value (URV) = 100 mbar
Nominal value (URL) = 500 mbar
Turn down:
•TD = URL /URV:1
set span:
URV – LRV = 100 mbar
This span is based on the zero point.
P01-xxxxxxxx-05-xx-xx-xx-001
Example: 500 mbar sensor
Case 2:
Lower range value Upper range value
Example:
Lower range value (LRV) = –300 mbar
Upper range value (URV) = 0 bar
Nominal value (URL) = 500 mbar
Turn down:
•TD = URL / (LRV) = 1.67:1
set span:
URV – LRV = 300 mbar
This span is based on the zero point.
P01-xMD7xxxx-05-xx-xx-xx-007
Example: 500 mbar sensor
1 Set span
2 Zero based span
3 Nominal value i Upper range limit (URL)
4 Nominal measuring range
5 Sensor measuring range
LRL Lower range limit
URL Upper range limit
LRV Lower range value
URV Upper range value
–500 mbar
0
+500 mbar
100
LRL
LRV
URL
URV
=
–500 mbar
+500 mbar
LRV
URLURV
0
LRL
–300 mbar
=