Operating menu and parameter description iTEMP TMT82
100 Endress+Hauser
Navigation Expert → Sensor → Diagnostic settings → Calibration counter start
Description Option to control the calibration counter.
The countdown duration (in days) is specified with the Calibration counter start
value parameter.
The status signal issued when the limit value is reached is defined with the
Calibration alarm category parameter.
Options Off: Stops the calibration counter
On: Starts the calibration counter
Reset + run: Resets to the set start value and starts the calibration counter
Factory setting Off
Calibration alarm category
Navigation Expert → Sensor → Diagnostic settings → Calibration alarm category
Description Use this function to select the category (status signal) as to how the device reacts when
the set calibration countdown expires.
Options Maintenance required (M)
Failure (F)
Factory setting Maintenance required (M)
Calibration counter start value
Navigation Expert → Sensor → Diagnostic settings → Calibration counter start value
Description Use this function to set the start value for the calibration counter.
User entry 0 to 365 d (days)
Factory setting 365
Calibration countdown
Navigation Expert → Sensor → Diagnostic settings → Calibration countdown
Description Use this function to view the time remaining until the next calibration.
Calibration countdown only runs when the device is active. Example: If the calibration
counter is set to 365 days on January 1, 2011 and no electricity is supplied to the
device for 100 days, the alarm for the calibration appears on April 10, 2012.