Operating menu and parameter description iTEMP TMT82
102 Endress+Hauser
User entry 0 ... 63
Factory setting 0
Additional information The measured value can only be transmitted via the current value is the address is set to
"0". The current is fixed at 4.0 mA for all other addresses (Multidrop mode).
No. of preambles
Navigation Expert → Communication → HART configuration → No. of preambles
Description Use this function to define the number of preambles in the HART telegram
User entry 2 ... 20
Factory setting 5
Configuration changed
Navigation Expert → Communication → HART configuration → Configuration changed
Description Indicates whether the configuration of the device has been changed by a master (primary
or secondary).
Reset configuration changed flag
Navigation Expert → Communication → HART configuration → Reset configuration changed flag
Description The Configuration changed information is reset by a master (primary or secondary).
"HART info" submenu
Device type
Navigation Expert → Communication → HART info → Device type
Description Use this function to view the device type with which the device is registered with the HART
FieldComm Group. The device type is specified by the manufacturer. It is needed to assign
the appropriate device description file (DD) to the device.
Display 2-digit hexadecimal number