iTEMP TMT82 Operating menu and parameter description
Endress+Hauser 107
Navigation Expert → Communication → Burst configuration → Burst mode
Description Activation of the HART burst mode for burst message X. Message 1 has the highest
priority, message 2 the second-highest priority, etc.
Options Off
The device only sends data to the bus at the request of a HART master
On
The device regularly sends data to the bus without being requested to do so.
Factory setting Off
Burst command
Navigation Expert → Communication → Burst configuration → Burst command
Prerequisite This parameter can only be selected if the Burst mode option is enabled.
Description Use this function to select the command whose answer is sent to the HART master in the
activated burst mode.
Options Command 1
Read out the primary variable
Command 2
Read out the current and the main measured value as a percentage
Command 3
Read out the dynamic HART variables and the current
Command 9
Read out the dynamic HART variables including the related status
Command 33
Read out the dynamic HART variables including the related unit
Factory setting Command 2
Additional information Commands 1, 2, 3 and 9 are universal HART commands.
Command 33 is a "Common-Practice" HART command.
More details on this are provided in the HART specifications.
Burst variable n
n = Number of burst variables (0 to 3)
Navigation Expert → Communication → Burst configuration → Burst variable n
Prerequisite This parameter can only be selected if the Burst mode option is enabled.