Operating menu and parameter description iTEMP TMT82
108 Endress+Hauser
Description Use this function to assign a measured variable to slots 0 to 3.
This assignment is only relevant for the burst mode. The measured variables are
assigned to the 4 HART variables (PV, SV, TV, QV) in the HART output →  104
menu.
Options Sensor 1 (measured value)
Sensor 2 (measured value)
Device temperature
Average of the two measured values: 0.5 x (SV1+SV2)
Difference between sensor 1 and sensor 2: SV1-SV2
Sensor 1 (backup sensor 2): If sensor 1 fails, the value of sensor 2 automatically becomes
the primary HART
®
value (PV): sensor 1 (OR sensor 2)
Sensor switching: If the value exceeds the configured threshold value T for sensor 1, the
measured value of sensor 2 becomes the primary HART
®
value (PV). The system
switches back to sensor 1 if the measured value of sensor 1 is at least 2 K below T:
sensor 1 (sensor 2, if sensor 1 > T)
The threshold value can be set with the Sensor switching limit value parameter.
With temperature-dependent switching, it is possible to combine 2 sensors that offer
advantages in different temperature ranges.
Average: 0.5 x (SV1+SV2) with backup (measured value of sensor 1 or sensor 2 in the
event of a sensor error in the other sensor)
Factory setting Burst variable slot 0: sensor 1
Burst variable slot 1: device temperature
Burst variable slot 2: sensor 1
Burst variable slot 3: sensor 1
Burst trigger mode
Navigation Expert → Communication → Burst configuration → Burst trigger mode
Prerequisite This parameter can only be selected if the Burst mode option is enabled.
Description Use this function to select the event that triggers burst message X.
Continuous:
The message is triggered in a time-controlled manner, at least observing the time
interval defined in the "Burst min period X" parameter.
Window:
The message is triggered if the specified measured value has changed by the value
defined in the "Burst trigger level X" parameter.
Rising:
The message is triggered if the specified measured value exceeds the value in the
"Burst trigger level X" parameter.
Falling:
The message is triggered if the specified measured value falls below the value in
the "Burst trigger level X" parameter.
On change:
The message is triggered if a measured value of the message changes.