Mounting Liquiphant FTL62 HART
14 Endress+Hauser
Enamel-coated tuning fork
~17 (0.67)
D
A
~14 (0.55)
C
D
D
~5 (0.2)
B
A0043327
 6 Typical switch points, enamel-coated tuning fork. Unit of measurement mm (in)
A Installation from above
B Installation from below
C Installation from the side
D Switch point
5.1.3 Take viscosity into consideration
Low viscosity
Low viscosity, e.g. water: < 2 000 mPa⋅s
It is permitted to position the tuning fork within the installation socket.
> 25 (0.98)
> !50 (1.97)
A0042204
 7 Installation example for low-viscosity liquids. Unit of measurement mm (in)
High viscosity
NOTICE
Highly viscous liquids may cause switching delays.
Make sure that the liquid can run off the tuning fork easily.
Deburr the socket surface.
High viscosity, e.g. viscous oils: ≤ 10 000 mPa⋅s
The tuning fork must be located outside the installation socket!