System integration Liquiphant FTL62 HART
30 Endress+Hauser
8 System integration
8.1 Overview of device description files
Manufacturer ID: 17 (0x11)
Device type code: 0x11C4
Device revision: 1
HART specification: 7
DD revision: 1
Device description files (DTM, DD) information and files at:
www.endress.com
www.fieldcommgroup.org
HART load: min. 250 Ω
8.2 Measured variables via HART protocol
The following measured values are assigned to the device variables at the factory:
Device variable Measured value
Primary variable (PV) parameter (Primary variable)
1)
Level limit detection
2)
Secondary variable (SV) parameter (Secondary variable) Sensor frequency
3)
Tertiary variable (TV) parameter (Third variable) Fork state
4)
Quaternary variable (QV) parameter (Quaternary variable) Sensor temperature
1) Primary variable (PV) parameter is always applied to the current output.
2) Level limit detection is the initial state depending on the fork state (uncovered/covered) and the safety
function (MIN/MAX)
3) Sensor frequency is the oscillation frequency of the fork
4) Fork state is the fork state (Fork covered/Fork uncovered)
The assignment of the measured values to the device variables can be changed in the
following submenu:
Navigation: Application → HART output → HART output
In a HART Multidrop loop, only one device may use the analog current value for signal
transmission. For all other devices in the Loop current mode parameter, select the
Disable option.
Navigation: Application → HART output → Configuration → Loop current mode →
Disable option
8.2.1 Device variables and measured values
The following codes are assigned to the device variables at the factory:
Device variable Device variable code
Level limit detection 0
Sensor frequency 1
Fork state 2
Sensor temperature 3