EasyManua.ls Logo

Endress+Hauser Liquiphant FTL62 - Device Operation; Reading Device Locking Status; Reading Measured Values; Adapting to Process Conditions

Endress+Hauser Liquiphant FTL62
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Liquiphant FTL62 HART Operation
Endress+Hauser 37
10 Operation
10.1 Reading off the device locking status
Displaying active write protection in the Locking status parameter
Local display 
:
The symbol appears on the main page
Operating tool (FieldCare/DeviceCare)  :
Navigation: System → Device management → Locking status
10.2 Reading off measured values
All the measured values can be read off using the Measured values submenu.
Navigation: Application menu → Measured values submenu
10.3 Adapting the device to process conditions
The following menus are available for this purpose:
Basic settings in the Guidance menu
Advanced settings in:
Diagnostics menu
Application menu
System menu
10.3.1 Level limit detection
Operating as a point level switch in the 8/16 mA mode.
Output of point level:
8 mA (demand mode: MIN uncovered or MAX covered)
16 mA (OK status: MIN covered or MAX uncovered)
1. Navigation: Application → Sensor → Sensor configuration
2. Set the Mode of operation to Level limit detection.
3. Set the Safety function to MIN (dry-running prevention) or MAX (overfill protection),
according to the application.
4. Set the Density setting parameter according to the application (> 0.4 g/cm³, > 0.5 g/
cm³, > 0.7 g/cm³ ).
5. Optionally: Set the Switching delay uncovered to covered parameter and the
Switching delay covered to uncovered parameter.
10.3.2 Sensor frequency
Continuous operation in the 4 to 20 mA mode. Loop current proportional to oscillation
frequency of fork.
1. Navigation: Application → Sensor → Sensor configuration
2. Set the Mode of operation parameter to the Sensor frequency option.
3. Set the Density setting parameter according to the application (> 0.4 g/cm³, > 0.5 g/
cm³, > 0.7 g/cm³ ).
This is used to ensure that the Fork state parameter (covered/uncovered)
continues to be displayed correctly.
4. Navigation: Guidance → Commissioning

Table of Contents

Other manuals for Endress+Hauser Liquiphant FTL62

Related product manuals