Technical data Liquiphant FTL62 HART
54 Endress+Hauser
Sensor temperature
Terminal current
The terminal current is the read-back current on terminal block. Visibility depends on
order options or device settings
Terminal voltage
Visibility depends on order options or device settings
Supported functions
Burst mode
Additional transmitter status
Device locking
15.2.8 Wireless HART data
Minimum start-up voltage: 10.5 V
Start-up current: > 3.6 mA
Start-up time: < 8 s
Minimum operating voltage: 10.5 V
Multidrop current: 4 mA
15.2.9 Heartbeat Technology
Heartbeat Technology module
The software package consists of 3 modules. These three modules combined check,
evaluate and monitor device functionality and process conditions.
Heartbeat Diagnostics
Heartbeat Verification
Heartbeat Monitoring
15.3 Environment
15.3.1 Ambient temperature range
The following values apply up to a process temperature of +90 °C (+194). At higher
process temperatures, the permitted ambient temperature is reduced (see diagram).
Without LCD display: –40 to +70 °C (–40 to +158)
With LCD display: –40 to +70 °C (–40 to +158) with limitations in optical properties,
such as display speed and contrast
Can be used without limitations: –20 to +60 °C (–4 to +140 °F)
Optionally available:
–50 °C (–58 °F) with restricted operating life and performance
–60 °C (–76 °F) with restricted operating life and performance,
 Below –50 °C (–58 °F): devices can be permanently damaged