Electrical connection Liquiphant FTL62 HART
22 Endress+Hauser
Devices with optional overvoltage protection
Spark-over voltage: min. 400 V
DC
Tested: According to IEC/DIN EN 60079-14 sub chapter 12.3
(IEC/DIN EN 60060-1 chapter 7)
Nominal discharge current: 10 kA
Overvoltage category
Overvoltage category II
Pollution degree
Pollution degree 2
6.3.6 Wiring
L
WARNING
Supply voltage might be connected!
Risk of electric shock and/or explosion!
If the device is used in hazardous areas, make sure to comply with national standards
and the specifications in the Safety Instructions (XAs). The specified cable gland must
be used.
The supply voltage must match the specifications on the nameplate.
Switch off the supply voltage before connecting the device.
If necessary, the potential matching line can be connected to the outer ground terminal
of the transmitter before the device is connected.
A suitable circuit breaker should be provided for the device in accordance with IEC/EN
61010.
The cables must be adequately insulated, with due consideration given to the supply
voltage and the overvoltage category.
The connecting cables must offer adequate temperature stability, with due
consideration given to the ambient temperature.
Only operate the device with the covers closed.
Connect the device in the following order:
1. Release the cover lock (if provided).
2. Unscrew the cover.
3. Guide the cables into the cable glands or cable entries. Use a suitable tool with width
across flats AF24/25 (8 Nm (5.9 lbf ft)) for the M20 cable gland.
4. Connect the cable.
5. Tighten the cable glands or cable entries so that they are leak-tight. Counter-tighten
the housing entry.
6. Screw the cover securely back onto the connection compartment.
7. If fitted: tighten the screw of the cover lock using the Allen key 0.7 Nm (0.52 lbf ft)
±0.2 Nm (0.15 lbf ft).