Liquistation CSF48 Programming
71
Event Editor 1
If you have more than one event editor, the "Event editor" menu item appears often. Use the "Link" menu
item to configure the logical link between the signals.
Source of data Options
•None
• Binary input S:x
• Current input S:x
• Temperature input
• Fieldbus
(depending on the version and
sensor)
Factory setting
None
Select the input via which the activation event is to be
output.
The inputs are configured in the "Setup/Inputs" menu.
The binary inputs are only visible if they have been
configured accordingly (rainfall or flow).
Measured value Options (depends on sen-
sor/data source)
•None
• Totalized flow
• %0V AO 01
• %0V AO 02
• %0V AO 03
• %0V AO 04
• %0V DO 01
• %0V DO 02
• %0V DO 03
• %0V DO 04
• %0V DO 05
• %0V DO 06
• %0V DO 07
• %0V DO 08
Factory setting
None
Operating mode Options
• Upper limit
• Lower limit
• Within range
•Out of range
•Rate of change
Factory setting
Upper limit
Type of limit value monitoring:
• Limit value overshoot or undershoot
• Measured value within or outside a range
• Rate of change
Limit value Range of adjustment and fac-
tory setting
Depends on the measured value
Operating mode="Above limit check" or "Below limit
check"
• The event is triggered if the limit value +
hysteresis is exceeded for the switch-on duration.
• The event is reset again if the limit value -
hysteresis is undershot for the duration of the
switch-off delay at least.
Path: Menu/Setup/Sampling programs
Function Options Info