HART bus address
If Multidrop is active (Bus address > 0), the current at current output 1 is fixed at 4 mA.
Here, it does not matter what function has been assigned to the output (measured
value/controller etc.). Current simulation is no longer possible.
If you reset the device to the factory settings (Diagnostics/Systemtest/Reset/Factory
default), the bus address is not reset. Your setting is retained.
Cleaning
program(optional)
Options
•None
• Cleaning 1
• Cleaning 2
• Cleaning 3
• Cleaning 4
Factory setting
None
Decide whether the diagnostic message should trigger a
cleaning program.
You can define the cleaning programs under:
Menu/Setup/Additional functions/Cleaning.
Detail information Read only Here you can find more information on the diagnostic
message and instructions on how to resolve the
problem.
Path: Menu/Setup/General settings/Extended setup/HART
Function Options Info
Bus address 0 to 63
Factory setting
0
You can change the device address to integrate several
HART devices in a network (Multidrop mode).
Path: ... /Extended setup/Diagnostics settings/Diag. behavior (optional)
Function Options Info