EasyManua.ls Logo

Endress+Hauser Proline Promass F 500 - Configuring the Status Input

Endress+Hauser Proline Promass F 500
218 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Proline Promass F 500 Modbus RS485 Commissioning
Endress+Hauser 101
Signal mode
→  101
0/4 mA value
→  101
20 mA value
→  101
Current span
→  101
Failure mode
→  101
Failure value
→  101
Parameter overview with brief description
Parameter Prerequisite Description User interface / 
Selection / User
entry
Factory setting
Terminal number Shows the terminal numbers
used by the current input
module.
Not used
24-25 (I/O 2)
22-23 (I/O 3)
20-21 (I/O 4)
*
Signal mode The measuring device is not
approved for use in the
hazardous area with type of
protection Ex-i.
Select the signal mode for the
current input.
Passive
Active
Passive
0/4 mA value Enter 4 mA value. Signed floating-point
number
0
20 mA value Enter 20 mA value. Signed floating-point
number
Depends on country
and nominal
diameter
Current span Select current range for
process value output and
upper/lower level for alarm
signal.
4...20 mA
4...20 mA NAMUR
4...20 mA US
0...20 mA
Country-specific:
4...20 mA NAMUR
4...20 mA US
Failure mode Define input behavior in alarm
condition.
Alarm
Last valid value
Defined value
Alarm
Failure value In the Failure mode
parameter, the Defined value
option is selected.
Enter value to be used by the
device if input value from
external device is missing.
Signed floating-point
number
0
* Visibility depends on order options or device settings
10.3.7 Configuring the status input
The Status input submenu guides the user systematically through all the parameters that
have to be set for configuring the status input.

Table of Contents

Related product manuals