Proline Promass F 500 Modbus RS485 System integration
Endress+Hauser 89
9 System integration
9.1 Overview of device description files
9.1.1 Current version data for the device
Firmware version 01.00.zz On the title page of the Operating instructions
On the transmitter nameplate
Firmware version
Diagnostics → Device information → Firmware
version
Release date of firmware version 08.2016 ---
For an overview of the different firmware versions for the device →  174
9.1.2 Operating tools
The suitable device description file for the individual operating tools is listed in the table
below, along with information on where the file can be acquired.
Operating tool via service
interface (CDI) or Modbus
interface
Sources for obtaining device descriptions
FieldCare www.endress.com → Download Area
CD–ROM (contact Endress+Hauser)
DVD (contact Endress+Hauser)
DeviceCare www.endress.com → Download Area
CD–ROM (contact Endress+Hauser)
DVD (contact Endress+Hauser)
9.2 Compatibility with earlier model
If the device is replaced, the measuring device Promass 500 supports the compatibility of
the Modbus registers for the process variables and the diagnostic information with
previous models Promass 83. It is not necessary to change the engineering parameters in
the automation system.
Compatible Modbus registers: process variables
Process variable Compatible Modbus registers
Mass flow 2007
Volume flow 2009
Corrected volume flow 2011
Density 2013
Reference density 2015
Temperature 2017
Totalizer 1 2610
Totalizer 2 2810
Totalizer 3 3010