Commissioning Proline Promass F 500 Modbus RS485
128 Endress+Hauser
Parameter overview with brief description
Parameter Prerequisite Description Selection / User
entry
Factory setting
Format display A local display is provided. Select how measured values
are shown on the display.
• 1 value, max. size
• 1 bargraph + 1
value
• 2 values
• 1 value large + 2
values
• 4 values
1 value, max. size
Value 1 display A local display is provided. Select the measured value that
is shown on the local display.
• Mass flow
• Volume flow
• Corrected volume
flow
• Target mass flow
*
• Carrier mass flow
*
• Density
• Reference density
• Concentration
*
• Temperature
• Carrier pipe
temperature
*
• Electronic
temperature
• Oscillation
frequency 0
• Oscillation
amplitude 0
*
• Frequency
fluctuation 0
• Oscillation
damping 0
• Oscillation
damping
fluctuation 0
• Signal asymmetry
• Exciter current 0
• Totalizer 1
• Totalizer 2
• Totalizer 3
• Current output 1
• Current output 2
*
• Current output 3
*
Mass flow
0% bargraph value 1 A local display is provided. Enter 0% value for bar graph
display.
Signed floating-point
number
Country-specific:
• 0 kg/h
• 0 lb/min
100% bargraph value 1 A local display is provided. Enter 100% value for bar
graph display.
Signed floating-point
number
Depends on country
and nominal
diameter
Decimal places 1 A measured value is specified
in the Value 1 display
parameter.
Select the number of decimal
places for the display value.
• x
• x.x
• x.xx
• x.xxx
• x.xxxx
x.xx