Electrical connection Proline Promass F 500 Modbus RS485
52 Endress+Hauser
Connecting the connecting cable to the transmitter
N
i
c
h
t
u
n
t
e
r
a
r
e
ö
f
f
n
e
n
N
i
c
h
t
u
n
t
e
r
c
i
r
c
u
i
t
s
a
r
e
a
l
i
v
e
1.
2.
3.
6.
5.
10 (0.4)
3 mm
22 mm
7.
24 mm
A0029592
1. Loosen the securing clamp of the connection compartment cover.
2. Unscrew the connection compartment cover.
3. Push the cable through the cable entry . To ensure tight sealing, do not remove the
sealing ring from the cable entry.
4. Strip the cable and cable ends. In the case of stranded cables, also fit ferrules.
5. Connect the protective ground.
6. Connect the cable in accordance with the terminal assignment →  49.
7. Firmly tighten the cable glands.
This concludes the process for connecting the connecting cable.
8. Screw on the connection compartment cover.
9. Tighten the securing clamp of the connection compartment cover.
10. After connecting the connecting cable: After connecting the connecting cables:
Connect the signal cable and the supply voltage cable →  53.