7.6.2 Thermostat Equipment Settings
Select whether the reversing valve is on in cool or on in heat. The default is On in
Cool.
Set to Yes if the heat pump and auxiliary heat can be on at the same time
(common with auxiliary electric heat).
Set to No if the heat pump should be off when the auxiliary heat is on (common
with auxiliary fossil fuel heat).
Without outdoor temperature sensor:
If available, use the values for your specific equipment. Otherwise, use the
default values.
Heat Pump with outdoor temperature sensor:
HIGH: Set to the temperature above which the auxiliary heat is disabled.
The range is from -38°F (-39°C) to 122°F (50°C). A typical value is 50°F
(10°C).
LOW: Set to the temperature below which the heat pump is disabled. The
range is from -40°F (-40°C) to 120°F (49°C). A typical value is 32°F (0°C).