Select the number of degrees that the temperature must go
beyond a setpoint before changing between HEAT and COOL
mode when in AUTO mode.
The range is 0 °F (0 °C) to 6 °F (3 °C).
The default is 2 °F (1 °C).
Select the amount of time the thermostat will engage the
equipment to reach the setpoint temperature before the
scheduled setpoint time.
Set the Anticipation Time to 0 if you do not want the equipment
to turn on before the scheduled setpoint time.
The range is from 0 to 180 minutes.
The default is 60 minutes.
For multiple-stage equipment.
Select the amount of time the thermostat will allow the
equipment to reach the desired temperature in the current stage
before engaging the next heating or cooling stage.
The range is 0 to 180 minutes.
The default is 90 minutes.
6.2 Heat Pump Settings
Select whether the reversing valve is on in cool or on in heat.
The default is On in Cool.
Select the type of equipment (Conventional or Heat Pump), the
default is Conventional.
Select the number of cool stages from 0 to 2.
The default is 1.