EasyManua.ls Logo

Energate FZ100C - Heat Pump Settings

Energate FZ100C
76 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
THIS DOCUMENT CONTAINS CONFIDENTIAL INFORMATION PROPRIETARY TO ENERGATE INC. NO PART OF ITS CONTENTS MAY BE DISCLOSED OR CONVEYED TO,
USED BY, OR COPIED TO A THIRD PARTY WITHOUT PRIOR WRITTEN CONSENT BY ENERGATE INC. PRINTED COPIES WILL BE CONSIDERED UNCONTROLLED.
AW000873-G 23
HYSTERISIS
Select the number of degrees that the temperature must go
beyond a setpoint before changing between HEAT and COOL
mode when in AUTO mode.
The range is 0 °F (0 °C) to 6 °F (3 °C).
The default is 2 °F (1 °C).
Control
Equipment
Settings
ANTICIPATION
TIME
Select the amount of time the thermostat will engage the
equipment to reach the setpoint temperature before the
scheduled setpoint time.
Set the Anticipation Time to 0 if you do not want the equipment
to turn on before the scheduled setpoint time.
The range is from 0 to 180 minutes.
The default is 60 minutes.
Control
User Options
MAX RECOVERY
TIME
For multiple-stage equipment.
Select the amount of time the thermostat will allow the
equipment to reach the desired temperature in the current stage
before engaging the next heating or cooling stage.
The range is 0 to 180 minutes.
The default is 90 minutes.
Control
Equipment
Settings
6.2 Heat Pump Settings
Setting
Description
Pioneer
Menu
Foundation
Menu
REV. VALVE
Select whether the reversing valve is on in cool or on in heat.
The default is On in Cool.
Equipment
Type
Equipment
Settings
TYPE
Select the type of equipment (Conventional or Heat Pump), the
default is Conventional.
Equipment
Type
Equipment
Settings
# OF COOL
STAGES
Select the number of cool stages from 0 to 2.
The default is 1.
Equipment
Type
Equipment
Settings

Table of Contents

Related product manuals