Select the number of heat stages from 0 to 2 (3 for heat pumps).
The default is 1.
Select the minimum on/off time from 1 to 10 minutes.
The default is 3.
Note: A minimum of 2 minutes is recommended for a furnace and
3 minutes for heat pumps and air conditioners.
Select the number of degrees that the temperature must go
beyond a setpoint before changing between HEAT and COOL
mode when in AUTO mode.
The range is 0 °F (0 °C) to 6 °F (3 °C).
The default is 2 °F (1 °C).
Set to Yes if the heat pump and auxiliary heat can be on at the
same time (common with auxiliary electric heat).
Set to No if the heat pump should be off when the auxiliary heat is
on (common with auxiliary fossil fuel heat).
The default is Yes.
Heat Pump without outdoor temperature sensor:
If available, use the values for your specific equipment.
Otherwise, use the default values.
Heat Pump with outdoor temperature sensor:
HIGH: Set to the temperature above which the auxiliary heat is
disabled. The range is from -38°F (-39°C) to 122°F (50°C). A typical
value is 50°F (10°C).
LOW: Set to the temperature below which the heat pump is
disabled. The range is from -40°F (-40°C) to 120°F (49°C). A typical
value is 32°F (0°C).
Default values are High: 122°F (50°C) and Low: -40°F (-40°C).