ANTICIPATION
TIME
Select the amount of time the thermostat will engage the
equipment to reach the setpoint temperature before the
scheduled setpoint time.
Set the Anticipation Time to 0 if you do not want the equipment
to turn on before the scheduled setpoint time.
The range is from 0 to 180 minutes.
The default is 60 minutes.
Control
User Options
MAX RECOVERY
TIME
For multiple-stage equipment.
Select the amount of time the thermostat will allow the
equipment to reach the desired temperature in the current stage
before engaging the next heating or cooling stage.
The range is 0 to 180 minutes.
The default is 90 minutes.
Control
Equipment
Settings