2. Installation
150 RC700 / RC90 Option Fieldbus I/O Rev.14
14. Select [Fieldbus Master]-[Slaves].
15. Confirm that the following information the master controls are displayed.
ID : Fieldbus station ID of slave
Input Bytes : Number of inputs per slave (Bytes)
Output Bytes : Number of outputs per slave (Bytes)
Spel Inputs : Number of inputs per slave (Bits)
Spel Outputs : Number of outputs per slave (Bits)
“Encapsulation Inactivity Timeout”
Fieldbus EtherNet/IP master board manufactured by molex is not supported
“Encapsulation Inactivity Timeout” which is added by EtherNet/IP standard update.
If connecting the EtherNet/IP slave device that supports “Encapsulation Inactivity
Timeout”, connection will be disconnected due to inconsistency with standard update on
the above.
You need to change the set value of “Encapsulation Inactivity Timeout” on the Fieldbus
EtherNet/IP master board side.