MPC-6000 / MPC-7000 / RND-2 PROGRAMMING MANUAL
6
QUICK START
Automatic programming of a new system
This is the quickest way to get a system operational. After all of the devices, notification
appliances and option modules have been programmed and installed, check all wiring
for grounds, shorts and opens. Connect SLUs, SRUs, NACs and any other field wiring
to the panel.
Automatic programming is selected from the Technician Level. Below are the steps to
access the Technician Level.
Step Action Description
1 Press “Menu” and then press “More” until
the option “Tech. Level” is displayed.
2 Press “Tech. Level”. The display will show the entry
screen for the technician level
access password.
3 Enter the password on the keypad. The
default is “0 1 2 3 4 5”.
The password will be displayed as
“* * * * * *”.
4 Press “Enter” or “D”. The display will show the starting
screen of the Technician Level.
Once the Technician Level has been accessed, following are the steps to activate the
autoprogram function.
Step Action Description
1 Select “Edit” by pressing “4”. The display will show the first
screen of the Edit functions with
“Auto Pgm” as one of the options.
2 Select “Autoprgm” by pressing “7”. The display will show the
Autoprgm screen.
3 Start the autoprogram by pressing the “D”
key.
The display will show all of the
addresses being checked as the
auto program is performed. This
could take several minutes. As
each new device is found, the
display will allow the installer to
chose whether to include the found
device. When the autoprogram is
finished, the screen will return to
the Edit options.