MPC-6000 / MPC-7000 / RND-2 PROGRAMMING MANUAL
15
Activating a Recall
It is possible to sound a Recall from the keypad using the following steps:
Action Result
1. Press “Menu”.
2. Press “More”.
3. Press “Recall”. Display requests “Yes/No” confirmation of the
Recall.
4. Press “Yes” to activate a Recall. The display will indicate Recall has been
activated.
5. Press “System Reset” to stop. Returns to system normal display.
Performing a Lamp Test
It is possible to perform a lamp test of the LEDs on the front of the Panel by following
the steps below:
Action Result
1. Press “Menu”.
2. Press “More”.
3. Press “More.”
4. Press “Lamp Test”. LEDs in the front panel will be lit for
approximately 3 seconds.
Viewing the Event History
The Event History screen displays the last 2000 events reported to a panel. The
information displayed includes the date and time, the type of event (TRB, ALM, SUP
etc.), the device reporting the event and the event reported.
Action Result
1. Press “Menu”.
2. Press “More”.
3. Press “More.”
4. Press “View History”. The display will show the most recent event.
5. Press the two buttons to the left of the display to
scroll forward and backward through the events.
(Press M1 to go to an older event, press M2 to
go to a more recent event.)
6. Press the upper right hand button (M3) to
escape back to the user menu.