MPC-6000 / MPC-7000 / RND-2 PROGRAMMING MANUAL
25
Technician Level
The Technician level allows complete programming of the MPC-6000/MPC-7000/RND-
2. See the User level functions for the method to access the Technician level. The steps
below assume that the Technician level has been accessed and that the panel is
displaying the starting screen of the Technician level.
Activating the Releasing Application Features
During initial power-up, the releasing application features are defaulted to NOT
INSTALLED state and need to be activated to use the panel for releasing application.
When this feature is activated, it allows the user to select releasing application features
at various levels of programming.
Action Result
1. From Tech Level Screen, select “Edit”. Enter the Edit Backup Screen.
2. Select “Manual Pgm”. Enter the Manual Programming Screen.
3. Select “Cmor,” then select “Sys Params.” Enter the System Parameter Programming
Screen.
4. Select “Cmor” three times then select
“Releasing.”
Enter the Releasing Application Prompt. Select
YES to enable the releasing application feature.
5. Press Bsav to save the selection. Saves the selection to the Backup program.
Configuring the Releasing Application Features
After the releasing application features have been activated, its parameters need to be
configured.
Action Result
1. From Tech Level Screen, select “Edit”. Enter the Edit Backup Screen.
2. Select “Manual Program.” Enter the Manual Programming Screen.
3. Select “Cmor,” then select “Releasing.” Enter the Releasing Parameter Programming
Screen
.
4. After configuring the Releasing Application
Parameters, press Bsav to save the selections.
Saves the selection to the Backup program.
The following provides a description of the releasing application parameters.
Parameters Sublevel Description
Agent Rel
Delay
Enter the desired time using the
numeric keypad in 5 sec.
Increments.
This parameter sets the time delay before the
releasing circuits activate once the releasing set
thresholds are met.
(Default – 30 sec.) Range: 0-
90 seconds.
Shutoff
Period
Enter the desired time using the
numeric keypad in 5 sec.
increments.
This parameter sets the time the releasing circuit is
active. This timer starts as soon as releasing circuit
activates. (Default – 60 sec.) Range: 20-60 seconds.
Abort
Type
ULI
IRI
*
AHJ
NYC
This parameter determines the action of the
panel when the abort switch is initiated while the
system is in Pre-Discharge condition.
ULI - Abort condition is initiated during Pre-
Discharge condition only. Pre-Discharge delay
counts down or restores to 10 sec. then holds if
abort is pressed and resumes countdown if abort
switch is released.