Printing the Sensitivity Levels (For Diagnostics Test Only)
The sensitivity levels of all of the detectors in the system may be printed. Follow the
steps below:
Action Result
1. Press “More”.
2. Press “Print Sensor Levels”. The display will indicate that the sensor levels
are being printed.
Editing the System Label
The system label may be changed as follows:
Action Result
1. Press “More”.
2. Press “More”.
3. Press “Edit Labels”.
4. Press “System”. The display will show the system label.
5. Use the keypad
keys to change the
system label
text. Pressing Bsav will save the changes.
Editing the Device Labels
The device labels may be changed as follows:
Action Result
1. Press “More”.
2. Press “More”.
3. Press “Edit Labels”.
4. Press “Device”.
5. Enter the Loop and Device address, then press
Dnxt.
The display will show the label for the device at
this address.
6. Use the keypad
keys to change the
device label
text. Pressing Bsav will save the changes.
Starting Quick Test
The Quick Test mode allows quick and easy testing of the installation. It will allow the
devices to be activated and the NACs to sound for an adjustable time of from 1-30
minutes.
Action Result
1. Press “Quick Test”.
2. Press “Start”. The display will prompt for a “Yes” or “No”
confirmation to start Quick Test.
3. Press “Yes” to start Quick Test. The display will show NAC sound time, the
status of the printer and the time until autoexit.
4. Press “Stop” to reset the panel.
Note: A test will reset the autoexit time to its original setting.