MPC-6000 / MPC-7000 / RND-2 PROGRAMMING MANUAL
12
Monitor Modules with relay and single input
Parameter Description
Label Generic label identifying the detector by loop number and address.
Led off LED will be defaulted to ON.
Input Usage Input usage will be defaulted to alarm.
Input Group Inputs will be defaulted to input group 241 (General Alarm).
Network Group This will not be set and will need to be set manually. (Future use)
Output Type Will be defaulted to non-silenceable.
Output Zone Will be defaulted to 1.
Intelligent LEDs
Parameter Description
Label Generic label identifying the detector by loop number and address.
Output Type Will be defaulted to non-silenceable.
Output Zone Will be defaulted to 1.
NACs
Parameter Description
Notification
Device Type
Set to Audible.
Output Type Will be defaulted to silenceable.
Output Zone Will be defaulted to 1.
Always On Will be no.
Wire Class Will be defaulted as Class B.
Default Times ON time delay will be defaulted to no delay.
OFF time delay will be defaulted to no delay.
The ON time and OFF time refer to the time delays in which the NAC delays its activation and
deactivation.
System Parameter
Parameter Description
Label Set to “FARADAY AUTO Prgrmd”
Drill Enable ON
Auto Silence Timer Off
Alarm Silence Inhibit Off
Panel Reset Inhibit Off
Auto Alarm silence Off
Trouble Reminder 12 hours
NAC sound time 5 seconds
Quick test exit 30 minutes
City Tie Activation Not changed
Global Commands Not changed
Printer ESC Not changed
Releasing Not installed. If installed, this activates releasing application features.
The presence of RDC-2 Annunciators is detected and their address is programmed
automatically when the system is initialized.