Formula for cable lengths:
L
≤
(
V
Omin
−
V
TERMINAL
min
) ⋅
A
⋅ κ
Cu
2 ⋅
I
2
+
I
1
This means:
• V
TERMINAL
= 24 V
±
10%,
minimum:
V
TERMINALmin
≥
21.6 V
• V
Omin
= Minimum operating voltage
supply (at power unit)
• Current I
1
= Current for electronic
components and inputs
• Current I
2
= Current for outputs/valves
• A = Cable cross section
(uniform e.g. 1.5 mm
2
)
• κ = Conductance value of cables
(uniform e.g.
κ
Cu
= 56
m
mm
2
⋅ Ω
)
Example
I
1
=1 A;
I
2
= 5 A;
V
O
= 24 V;
V
TERMINALmin
= 21.6 V ;
κ
Cu
= 56
m
mm
2
⋅ Ω
;
Result
L ≤ 18 m for A = 1.5 mm
2
L ≤ 30 m for A = 2.5 mm
2