Formula for cable lengths:
L
(
V
Omin
V
TERMINAL
min
)
A
κ
Cu
2
I
2
+
I
1
This means:
V
TERMINAL
= 24 V
±
10%,
minimum:
V
TERMINALmin
21.6 V
V
Omin
= Minimum operating voltage
supply (at power unit)
Current I
1
= Current for electronic
components and inputs
Current I
2
= Current for outputs/valves
A = Cable cross section
(uniform e.g. 1.5 mm
2
)
κ = Conductance value of cables
(uniform e.g.
κ
Cu
= 56
m
mm
2
)
Example
I
1
=1 A;
I
2
= 5 A;
V
O
= 24 V;
V
TERMINALmin
= 21.6 V ;
κ
Cu
= 56
m
mm
2
;
Result
L 18 m for A = 1.5 mm
2
L 30 m for A = 2.5 mm
2