112 MS-9200UDLS/E/C Manual — P/N 52750:F 7/26/2010
Programming Master Programming Level
While viewing the selected screen, press the number corresponding to the desired relay type to
program the main circuit board relay. The choice will be stored in memory and the display will
return to the Relay Type Screen which will show the programmed type choice. Press the Escape
key to return to the Relays Selection Screen and repeat the preceding procedure for the remaining
relays.
Canadian Option
Pressing 1 while viewing System Setup Screen #3 will configure the FACP to comply with
Canadian requirements. The display will change to Canadian Opt. On. Each press of the 1 key
will cause the display to toggle between Canadian Opt. On and Canadian Opt. Off.:
Important! For Canadian Applications, this option must be set to ON prior to any other panel
programming.
The Canadian Options configures the FACP with the following as required by Canada:
The following monitor module type codes are not available:
monitor
non-latching supervisory
non-latching drill
non-latching process monitor
process monitor
hazard
tornado
medical alert
The auto-silence timer is fixed at 20 minutes and cannot be changed.
Addressable ionization smoke detector sensitivity is automatically monitored using Canadian
specifications.
Positive Alarm Sequence, the Pre-Signal option, and the Silence Inhibit Timer are not
available for Canadian applications.
Waterflow Silenceable
Pressing 2 while viewing System Setup Screen #3 will allow the programmer to configure the
system for silenceable on nonsilenceable waterflow circuits. Each press of the 2 key will toggle the
display between Waterflow Sil. No and Waterflow Sil. Yes. When Waterflow Sil. No is selected, all
output devices associated with a waterflow type input device, will be nonsilenceable. When
Waterflow Sil. Yes is selected, all output devices associated with a waterflow type input device, will
be silenceable.
NOTES:
1. AR (AutoResettable) in SUPERVISORY AR and PROCMON AR means that a relay with the
Supervisory and/or Process Monitor type code, when activated, will automatically reset when the
corresponding condition is cleared.
2. A relay programmed with the Silenceable Alarm type will activate upon any alarm and
deactivate when the FACP Alarm Silenced LED is illuminated.
SYSTEM SETUP
1=CANADIAN OPT. OFF
2=WATERFLOW SIL. NO
System Setup Screen #3
SYSTEM SETUP
1=CANADIAN OPT. OFF
2=WATERFLOW SIL. NO