EasyManua.ls Logo

Fire-Lite MS-9200UDLS - 2: Printer; Installation

Fire-Lite MS-9200UDLS
232 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
58 MS-9200UDLS/E/C Manual — P/N 52750:F 7/26/2010
Installation Optional Module Installation
2.9.2 Printer
A serial printer may be connected to TB8 Terminals 1 - 4 on the FACP when TB8 is not being used
for annunciators or a local PC connection. The printer can be used to provide a hard-copy printout
of real-time events, history file and walktest data. Installation the device requires panel program-
ming to allow the FACP to communicate with the device.
A parallel printer may also be connected to the FACP using the optional ANN-S/PG Serial/Parallel
Interface Module. Refer to “ANN-S/PG Serial/Parallel Interface Installation” on page 30 for
installation details. Refer to “ANN-BUS Options” on page 120 for programming information.
Installation
Serial printers and PCs require separate primary power. Also required is the serial
PRT/PK-CABLE which is an interface cable prewired to a DB9F connector. Wire the PRT/PK-
CABLE to TB8 Terminals 1 - 4 as illustrated in the following figure. Connect the DB9F connector
to the printer or PC serial EIA-232 port. If a nine-pin serial connector is not available on the printer
or PC, use a DB25 adapter. Make certain that the DB25 adapter does not swap the Transmit and
NO NC C NC NO C
TB5
TB9
TB8TB6
TB10
PH15
PRI. PHONE LINE
SEC. PHONE LINE
PH16
J12
SW1
J5
J6
JP3
4XTM
Xmt Rcv Dtr Gnd
A B
In+ In- Out+ Out-
+ -
A B
B+ A+ B- A- A B
Slc Slc Slc Slc Shield
J7
Figure 2.16 4XTMF Connectors to MS-9200UDLS Connectors
J5 & J6 Connectors
C
u
t
Ju
m
p
e
r
JP
3
Standoff Standoff
4XTMF
FACP main circuit board
9
2
u
d
l
s
c
4
x
t
m
.
w
m
f
NOTE: Jumper JP2 on the FACP main circuit board can be used to configure the FACP
supervisory relay for operation with the 4XTMF module. Relay 3 at TB5 must be programmed as
a supervisory relay.
Cutting JP2 will allow the 4XTMF to generate a trouble if the supervisory contact opens
Leaving JP2 in will prevent generation of a trouble if the supervisory contact opens.
!
CAUTION: POSSIBLE EQUIPMENT DAMAGE
DO NOT CONNECT A PRINTER OR PC TO THE MS-9200UDLS FACP IF A GROUND FAULT
(ZERO IMPEDANCE TO GROUND) EXISTS ON THE CONTROL PANEL. CIRCUIT DAMAGE
MAY RESULT. REMOVE ALL POWER (PRIMARY AND SECONDARY) BEFORE INSTALLING OR
REMOVING ANY WIRING.

Table of Contents

Other manuals for Fire-Lite MS-9200UDLS

Related product manuals