136 MS-9200UDLS/E/C Manual — P/N 52750:F 7/26/2010
Programming Master Programming Level
Central Station
Central Station programming configures the control panel DACT for contacting the central station.
Pressing 2 while viewing On Board DACT Screen #2 will cause the following screens to be
displayed:
Reporting Enable
To enable the DACT for reporting FACP activity to the central station, press 1 while viewing
Central Station Screen #1 so the display reads Reporting Enabled. Each press of the 1 key will
toggle the display between Reporting Disabled and Reporting Enabled.
Trouble Call Limit (Dialer Runaway Prevention)
The Call Limit option limits the number of DACT trouble calls to the Central Station, to a
programmed amount between 0 and 99, for each unique trouble within a 24 hour period. Separate
limit counters keep track of each unique type of trouble. Note that the number of phone line
(communication) faults called to the Central Station are not limited by this feature. No subsequent
restoral message is sent to the Central Station(s) for a particular trouble whose call limit has been
reached. Local DACT annunciation will still track the particular trouble and restoral.
ON BOARD DACT
1=SERVICE TERMINAL
2=CENTRAL STATION
3=SUPERV PHONE LINE
On Board DACT Screen #2
CENTRAL STATION
1=REPORTING DISABLED
2=REPORT BACKUP
3=CALL LIMIT
Central Station Screen #1
CENTRAL STATION
1=PRIMARY
2=SECONDARY
3=REPORT STYLE
Central Station Screen #2