Generator Failure
16.1.15 Kapitel/Chapter 8: Generator Failure - Seite/Page 149
8.3 Environmental protection
Environmental protection.Danger to the environment due to mishandling!
Significant environmental damage can occur, particularly for
incorrect disposal, if environmentally hazardous operating
materials are mishandled. Therefore:
• Always observe the instructions mentioned below.
• Take immediate action if environmentally hazardous
materials reach the environment. Inform the responsible
local authorities about the damage in the case of doubt.
The disposal must be performed by a specialist disposal company.
8.4 Tools and measuring instruments
In order to be able to manage disturbances while driving, following tools and measuring instruments should
belong to the equipment on board:
• Multimeter for voltage (AC), frequency and resistance
• Measuring instrument for inductance
• Measuring instrument for capacity
• Current absorbing clamps
• Thermometer (ideal is a infrared thermometer)
• Pressure device (pincer) für coolant circuit
8.5 Overloading the Generator
Please ensure that the genset is not overloaded. This is especially the case with multi-power aggregates. Over-
loading occurs when the electrical load (demand) induces a load torque in the generator which is higher than what
the diesel drive motor can provide. Overloading causes the engine to run rough, burn oil, create excessive exhaust
(environmentally unfriendly) and even to stall.
The generator should only be loaded at the peak rated power for short periods only! A high peak current is required
to start many electrical devices, especially electric motors and compressors (from a still stand state).
In order to prolong the genset´s life expectancy, the nominal electrical demand on the system should not be more
than 70% of the rated genset power.
Bear this in mind when switching on electrical devices. This ensures a longer life expectancy.
Continuous performance is the uninterrupted running of the generator for many hours. The genset can be run for
several hours at partial load (i.e. 2/3 of rated power), however it is not advised that it is run for more than 2-3 hours
at full load.
The Panda is designed so as not to overheat even under extreme conditions. Note: The exhaust gas will become
sooty during peak-load operation.
8.5.1 Overloading the Generator with Electric Motors
Please note that electric motors require six to ten times more power than their rated capacity to start.
If the supplied generator power is lower than what the electric motor requires, the generator voltage will collapse. For
applications where a high current draw is required to start an electrical device (such as an electric motor), the motor