Warnings and error messages
Seite/Page 44 - Kapitel/Chapter 6: Warnings and error messages 20.10.22
6.2.3 Bus errors
If the communication connection is lost on the Fischer Panda bus, an error is output on the display after a period of
10 seconds:
Fig. 6.2.3-1: Error in the communication (Fischer Panda bus)This error will occur if at least one of the two data lines
of the Fischer Panda bus is disconnected. Once the
connection is restored, the error message can be
acknowledged with the start/stop button.
If the communication connection is lost, the generator shall be secured (open battery disconnect switches), and all
plug-in connections and cables shall be checked for firm seating or damage.
P45i vehicle 3x230V Cylinder head temperature
Delay
98 °C
5 s
105 °C
5 s
Winding temperature
Delay
130 °C
5 s
135 °C
5 s
Exhaust manifold temperature
Delay
100 °C
2 s
105 °C
2 s
P60i marine Cylinder head temperature
Delay
90 °C
5 s
95 °C
5 s
Winding temperature
Delay
130 °C
5 s
135 °C
5 s
Exhaust manifold temperature
Delay
70 °C
2 s
75 °C
2 s
P60i vehicle Cylinder head temperature
Delay
90 °C
5 s
95 °C
5 s
Winding temperature
Delay
130 °C
5 s
135 °C
5 s
Exhaust manifold temperature
Delay
95 °C
2 s
98 °C
2s
All generator types Starter battery voltage low
Delay
11.8 V
30 s
10.8 V
30 s
Starter battery voltage high 15.0 V
5 s
--
--
Generator type Warning/fault Warning threshold Fault threshold

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fischer Panda iControl3 and is the answer not in the manual?

Fischer Panda iControl3 Specifications

General IconGeneral
BrandFischer Panda
ModeliControl3
CategoryController
LanguageEnglish

Related product manuals