Operating Manual BA3002 EN
8 Repair
Page 53 of 79
8.3.2 Replacing Seals on the ROTADISK Pneumatic Actuator (RD 2,5160)
The ROTADISK Pneumatic Actuator is
taken out of operation (no compressed air supply is connected).
Disconnected from the valve and all other sub-assemblies (e.g. solenoid valve,
limit switch, position indicator or position controller.
1. Make different marks on the edges of both lids [2] on the top of the body.
The marks simplify correct installation of the ROTADISK Pneumatic Actuator after
disassembly.
Make sure that you do not adjust the nuts of the threaded pins/end stops so that the
pre-set end position setting and thus the angle of rotation of 90° ± 3° is retained.
2. Remove the lids [2] from the ROTADISK Pneumatic Actuator by loosening the lid
screws [1] on both sides of the body.
Use a suitable assembly device for this.
3. Move the pistons up to the inside stop by turning the drive shaft [4] on the outer
square bar.
[1]
[2]
[3]
[do not adjust!]