PV series Solar Pumping Inverter
- 45 -
Chapter Four Troubleshooting and Countermeasures
PV200 inverters supply many kinds of warning information and protection functions, when failure
occurred, function of protection actives, inverters will stop output, fault relay contact of inverter active,
and display the fault code on inverter operation panel. Before asking support, users can self-check
according to this chapter tips, and analyze the fault reasons, get the solutions. If fault still can’t be
solved, please ask for service, contact with agents or directly to ADA.
Operator
Panel
Displays
Fault Name
Fault Reasons
Troubleshooting
Err01
Acceleration
Overcurrent
1Inverter output circuit
grounding or shorted
2Acceleration time is too
short
3Manually boost the torque or
V/F curve unsuitable
4Voltage is too low
5Start the rotating motor
6Shock load on acceleration
7Inverter selection is too
small
1Peripheral
troubleshooting
2Prolong the acceleration
time
3Adjust the V/F curve
Or manually-torque-boost
4The voltage adjusted to a
normal range
5Select start on
rotational-speed tracking or
waiting for motor stopped
6Cancel shock-load
7Select inverter with a
larger power
Err02
Deceleration
Overcurrent
1Inverter output circuit
grounding or shorted
2Deceleration time is too
short
3Voltage is too low
4Shock load on deceleration
5No installation of braking
resistor
1Peripheral
troubleshooting
2Prolong the deceleration
time
3The voltage adjusted to a
normal range
4Cancel shock-load
5Install braking resistor
Err03
Constant-speed
Overcurrent
1Inverter output circuit
grounding or shorted
2Voltage is too low
3If there is shock-load during
running
4Inverter selection is too
1Peripheral
troubleshooting
2The voltage adjusted to a
normal range
3Cancel shock-load
4Select inverter with a