PV series Solar Pumping Inverter
- 48 -
Cancel the
self-identification
1、Press the button of
STOP/RST during
self-identification
1、Press STOP/RST for
restoration
Self-identification
failure
1、Motor and the inverter
output terminals are not
connected
2、Motor connects to load
3、Motor Failure
1、Check the wirings
between inverter and motor
2、Motor breaks away from
load
3、Check motor
485
Communication
Timeout
1、Upper computer works
abnormally
2、Communication cable is
abnormal
3、F15 communication
parameters set incorrectly
1、Check the wirings of
upper computer
2、Check the
communication cable
3、Set the communication
parameters correctly
PID feedback
disconnection on
running
1、PID feedback lower than the
value set by F13.24
1、Check the PID feedback
signal or set F13.24 to be a
suitable value
1、Setting the function of
running time arrives
1、Refer to description of
F05.14
1、Copy card uninstalled or
plugged unsuitable
2、Parameters copy card
abnormal
3、Control board abnormal
1、Parameter copy card
installed correctly
2、Ask for technical support
3、Ask for technical support
1、 1、Copy card uninstalled or
plugged unsuitable
2、Parameters copy card
abnormal
3、Control board abnormal
1、Parameter copy card
installed correctly
2、Ask for technical support
3、Ask for technical support
1、Braking wirings fault or
braking tube damaged
2、Value of external braking
resister is too small
1.Check the brake unit, and
replace the new brake tube
2.Increasing the braking
resistor
Disconnection
Fault of
temperature
sensor
1、Temperature sensor failure
or cable break
1、Ask for technical support
1、Running current of inverter
is less than F11.22
1、Confirm whether the load
loss or parameters of