PV series Solar Pumping Inverter
- 48 -
Err16
Cancel the
self-identification
1Press the button of
STOP/RST during
self-identification
1Press STOP/RST for
restoration
Err17
Self-identification
failure
1Motor and the inverter
output terminals are not
connected
2Motor connects to load
3Motor Failure
1Check the wirings
between inverter and motor
2Motor breaks away from
load
3Check motor
Err18
485
Communication
Timeout
1Upper computer works
abnormally
2Communication cable is
abnormal
3F15 communication
parameters set incorrectly
1Check the wirings of
upper computer
2Check the
communication cable
3Set the communication
parameters correctly
Err19
PID feedback
disconnection on
running
1PID feedback lower than the
value set by F13.24
1Check the PID feedback
signal or set F13.24 to be a
suitable value
Err20
The running time
arrives
1Setting the function of
running time arrives
1Refer to description of
F05.14
Err21
Parameter
Upload Error
1Copy card uninstalled or
plugged unsuitable
2Parameters copy card
abnormal
3Control board abnormal
1Parameter copy card
installed correctly
2Ask for technical support
3Ask for technical support
Err22
Parameter
Download Error
1 1Copy card uninstalled or
plugged unsuitable
2Parameters copy card
abnormal
3Control board abnormal
1Parameter copy card
installed correctly
2Ask for technical support
3Ask for technical support
Err23
Braking Unit
failure
1Braking wirings fault or
braking tube damaged
2Value of external braking
resister is too small
1.Check the brake unit, and
replace the new brake tube
2Increasing the braking
resistor
Err24
Disconnection
Fault of
temperature
sensor
1Temperature sensor failure
or cable break
1Ask for technical support
Err25
Inverter
loss-load
1Running current of inverter
is less than F11.22
1Confirm whether the load
loss or parameters of