FRICK
®
QUANTUM™ LX COMPRESSOR CONTROL PANEL S90-020 M
MAINTENANCE Page 23
Current Transformer (Motor Amps)
Channel 16 of Enhanced Analog Board 1 is dedicated to
reading motor amps, either through the use of the on
board current transformer, or from an external source.
When reading motor amps directly, the input signal cannot
exceed 5
amps. If you are using an external current transformer,
remove the jumper at Link 2, and connect the wiring to
connector P8. If you intend on utilizing the on-board
current transformer, then install Link 2, and connect the
wiring to Channel 16, as shown in the diagram below:
P6B (Inputs)
(CH11) (CH12)
P4A (Inputs)
(CH1) (CH2)
P4B (Inputs)
(CH3) (CH4)
CH. 16
Current Transformer (CT)
connection - Standard direct
connection, 0 - 5 amp input
Install LK2
LK 2
Install this jumper when using
the on board Current
Transformer and connector P8 to
use CH. 16 (P8) to read Motor
Amps
Remove for CH. 16 external
Motor Amps signal and connect
to P7B directly
CH. 16
Motor Amps - Alternate external
signal connection, 0 - 50mA input
(Remove LK2)