22
[Setting example] Setting the operation value of alarm 2 to
-
10°C
Press and hold the
SEL
key for one second.
will be displayed on the PV display.
Press the key to display .
Press the
SEL
key once.
The current setting ( ) flashes on the SV display.
Press the or keys to display .
Press the
SEL
key once. will stop flashing and will be registered for . After that, the
controller will operate with the operation value of alarm 2 being
-
10°C.
If you want to display the operation status, press and hold the
SEL
key for two seconds.
Operating procedureDisplay
1.
2.
3.
4.
5.
6.
[Description]
• These parameters are used to for settings of alarm 1, 2
and 3.
• When the alarm type ( ,
or
) is set to
0 to 15, alarms 1, 2 and 3 ( ,
and
) can be
set.
• When the alarm type ( ,
or
) is set to
any value other than 0 to 15, the upper and lower limits
of alarm 1, 2 and 3 ( , ,
,
,
,
) can be set.
[Note]
Setting codes (12 to 15) cannot be selected in alarm
type 1 and 3 (
/
).
Related parameters: ,
,
(page 46)
,
,
(page 59)
,
,
(page 55)
,
,
(page 60)
(Setting range:
Absolute value alarm: 0 to 100%FS
Deviation value alarm:
-
100 to 100%FS )
(Option)
}
Setting alarm
1, 2 and 3
Upper limit of alarm
1, 2 and 3
Lower limit of
alarm 1,2 and 3