Fuji Electric Micro-controller X Series - Setting Value) Offset

Fuji Electric Micro-controller X Series
83 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
44
[Description]
•With this function, predetermined value is added to the origi-
nal SV. This parameter is used to eliminate the offset that
occurs in performing P control.
•The PXR operates based on the SV to which the SV offset
value is added.
SV (Setting value) offset (Setting range:
-
50 to 50%FS)
[Setting example] Adding the SV offset value of 9°C to the currently set value
Press and hold the
SEL
key for three seconds.
will be displayed on the PV display.
Press the
key to display
.
Press the
SEL
key once.
The current setting (
) flashes on the SV display.
Press the or key to display .
Press the
SEL
key once. will stop flashing and will be registered for
. (The displayed
SV remains unchanged.) After that, the controller will operate at the SV value to which the SV
offset value of 9°C is added.
If you want to display the operation status, press and hold the
SEL
key for two seconds.
Operating procedureDisplay
1.
2.
3.
4.
5.
6.
Alarm judgment is made by the displayed SV to which
the SV offset value is not added.