EasyManua.ls Logo

Fuji Electric Micro-controller X Series - PV (Measured Value) Offset

Fuji Electric Micro-controller X Series
83 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
43
[Description]
•With this function, predetermined value is added to the in-
put reading. This parameter is used for adjusting PXR’s
indication so that it becomes same as the one of the other
instruments like recorder.
PV (Measured value) offset (Setting range:
-
10 to 10%FS)
[Setting example] Adding the PV offset value of 5°C to the input value of 1200 °C
Press and hold the
SEL
key for three seconds.
will be displayed on the PV display.
Press the
key to display .
Press the
SEL
key once.
The current setting (
) flashes on the SV display.
Press the or key to display .
Press the
SEL
key once. will stop flashing and will be registered for . After that, the controller will
operate so that the value to which the offset value of 5°C is added can be brought close to the set value.
If you want to display the operation status, press and hold the
SEL
key for two seconds.
Operating procedureDisplay
1.
2.
3.
4.
5.
6.
•The PXR operates at the displayed PV (the value to which
the PV offset value is added).

Table of Contents

Related product manuals