40
[Description]
• These parameters are used for setting the lower and up-
per limits of the measured range and unit of temperature.
•A decimal point position can be set in the parameter of
.
•For the current and voltage inputs, , and can be set
for , and for other inputs, and can be set for
.
• See the right table for input range.
Setting the measuring range (Input range) (Setting range:
-
1999 to 9999)
Selection °C / °F (Settins: °C / °F)
J
J
K
K
K
R
B
S
T
T
E
E
N
PL-II
1 to 5 V DC
Thermocouple
Direct-curren
t
voltage
-1999 to 9999
(Scaling is possible)
* For 4 to 20mA DC input, connect the supplied resistance of 250Ω
between terminals !7 and !8 (in the case of PXR4), and between
terminals #5 and #6 (in the case of PXR5/9) to change to the 1 to
5V DC input.
[Note]
The input accuracy is ±0.5%FS±1 digit except the cases shown
below.
Thermocouple R at 0 to 500 °C:
Thermocouple B at 0 to 400 °C:
Other kinds of thermocouples: ±0.5% FS ± 1 digit ± 1 °C
150
300
500
600
100
200
600
850
400
800
400
800
1200
1600
1800
1600
200
400
800
800
1300
1300
Range
(°C)
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
0
0
0
0
-50
-100
-199
-199
0
0
0
0
0
0
0
0
-150
-150
0
-150
0
0
302
572
932
1112
212
392
1112
1562
752
1472
752
1472
2192
2912
3272
2912
392
752
1472
1472
2372
2372
Range
(°F)
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
32
32
32
32
-58
-148
-328
-328
32
32
32
32
32
32
32
32
-238
-238
32
-238
32
32
With / without
a decimal point
(°C)
O
O
O
O
O
O
O
X
O
O
O
O
X
X
X
X
O
O
O
O
X
X
Pt100Ω
Resistance
bulb JIS
(IEC)
Input type
*
With / without
a decimal point
(°F)
O
O
O
X
O
O
X
X
O
X
O
X
X
X
X
X
X
X
X
X
X
X
*
O: with
X: without
*
In this range, this controller may
display a wrong process value
because of the characteristecs of
the sensor.
w Input range table (Standard range)