EasyManua.ls Logo

Fuji Electric Monitouch V9 Series - Page 319

Fuji Electric Monitouch V9 Series
482 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
13-32 13. OMRON
13.2.2 E5AK-T
Communication Setting
Editor
Communication setting
(Underlined setting: default)
Temperature Controller
(Underlined setting: default)
Available Device Memory
The available setting range of device memory varies depending on the model. Be sure to set within the range available for the
model to be used. Use [TYPE] when assigning indirect device memory for macro programs.
Indirect Device Memory Designation
When monitoring special command S14 (status), specify the group number in the expansion code.
00H: Group A
01H: Group B
Item Setting Remarks
Connection Mode
1:1 / 1:n
/ Multi-link2 /
Multi-link2 (Ethernet) /
1:n Multi-link2 (Ethernet)
Signal Level RS-232C / RS-422/485
Baud Rate 4800 / 9600 / 19200 bps
Data Length 7
/ 8 bits
Stop Bit 1 / 2
bits
Parity None / Odd / Even
Targe t Port No. 0 to 99
Mode
Displayed
Character
Setting Data Setting
Option mode
Sbit Stop bit 1 / 2
bits
LEn Data length 7
/ 8 bits
Prty Parity None / Odd / Even
bPS Baud rate 4800 / 9600 / 19200 bps
U-no Communication unit No. 0
to 99
Device Memory TYPE Remarks
D (parameter) 00H
S (special command) 01H
S00 to 11 Write only, expansion code: fixed to 0
S14 Read only, expansion code 0: group A / 1: group B
P (program parameter) 02H
15 8 7 0
n+0 Model (91 to 98) Device type
n+1 Address No.
n+2 Expansion code Bit designation
n+3 00 Station number

Table of Contents