13-32 13. OMRON
13.2.2 E5AK-T
Communication Setting
Editor
Communication setting
(Underlined setting: default)
Temperature Controller
(Underlined setting: default)
Available Device Memory
The available setting range of device memory varies depending on the model. Be sure to set within the range available for the
model to be used. Use [TYPE] when assigning indirect device memory for macro programs.
Indirect Device Memory Designation
When monitoring special command S14 (status), specify the group number in the expansion code.
00H: Group A
01H: Group B
Item Setting Remarks
Connection Mode
1:1 / 1:n
/ Multi-link2 /
Multi-link2 (Ethernet) /
1:n Multi-link2 (Ethernet)
Signal Level RS-232C / RS-422/485
Baud Rate 4800 / 9600 / 19200 bps
Data Length 7
/ 8 bits
Stop Bit 1 / 2
bits
Parity None / Odd / Even
Targe t Port No. 0 to 99
Mode
Displayed
Character
Setting Data Setting
Option mode
Sbit Stop bit 1 / 2
bits
LEn Data length 7
/ 8 bits
Prty Parity None / Odd / Even
bPS Baud rate 4800 / 9600 / 19200 bps
U-no Communication unit No. 0
to 99
Device Memory TYPE Remarks
D (parameter) 00H
S (special command) 01H
S00 to 11 Write only, expansion code: fixed to 0
S14 Read only, expansion code 0: group A / 1: group B
P (program parameter) 02H
15 8 7 0
n+0 Model (91 to 98) Device type
n+1 Address No.
n+2 Expansion code Bit designation
n+3 00 Station number