13.2 Temperature Controller/Servo/Inverter Connection 13-57
13.2.13KM20
Communication Setting
Editor
Communication setting
(Underlined setting: default)
Temperature Controller
Communication setting switch
Unit No. setting switch
Item Setting Remarks
Connection Mode
1:1 / 1:n
/ Multi-link2 / Multi-link2 (Ethernet) /
1:n Multi-link2 (Ethernet)
Signal Level RS-232C / RS-422/485
Baud Rate 4800 / 9600 / 19200 / 38400 bps
Data Length 7
/ 8 bits
Stop Bit 1 / 2
bits
Parity None / Odd / Even
Targe t Port No. 0 to 99
COMMUNICATION SETTING SW Setting Data Remarks
SW1
SW2
SW3
Baud rate
SW4 Data bits
OFF: 7 bits
ON: 8 bits
SW5 Stop bit
OFF: 2 bits
ON: 1 bit
SW6
SW7
Parity
SW8 Priority setting
OFF: DIP switch setting
ON: RS-485 communication setting
CT/5ACT setting
SW9
SW10
Circuit setting
Set this switch correctly according to the
measurement environment.
Otherwise, measurement cannot be
performed correctly.
UNIT No. Setting Data Remarks
00 to 99
SW6 SW7 Circuit
OFF OFF Three-phase three-wire
ON OFF Single-phase two-wire
OFF ON Single-phase three-wire