15-16 15. Panasonic
15.1.5 FP7 Series (RS232C/422)
Communication Setting
Editor
Communication setting
(Underlined setting: default)
PLC
FP7 configuration
Make PLC settings using the programming tool “FPWIN GR7”.
For more information, refer to the PLC manual issued by the manufacturer.
(Underlined setting: default)
*1 When using communication cassettes, configure CH1 and CH2 as COM1 and COM2 respectively.
CH1 = COM1
CH2 = COM2
AFP7CCS2
AFP7CCM1/AFP7CCM2
Item Setting Remarks
Connection Mode
1:1
/ 1:n / Multi-link / Multi-link2 /
Multi-link2 (Ethernet) /
1:n Multi-link2 (Ethernet)
Signal Level RS-232C
/ RS-422/485
Baud Rate
4800 / 9600
/ 19200 / 38400 / 57600 /
115K bps
Data Length 7 / 8
bits
Stop Bit 1
/ 2 bits
Parity None / Odd
/ Even
Target Port No. 0 to 255
Setting Items Descriptions
Built-in SCU
COM0 setting
COM1 setting
*1
COM 2 setting
*1
Communication mode MEWTOCOL-7
Target p or t No. 1 to 255
Baud rate 4800 / 9600
/ 19200 / 38400 / 57600 / 115K bps
Data length 7 / 8
bits
Parity None / Odd
/ Even
Stop bit 1
/ 2 bits
CS/RS Invalid
Transmission latency setting
For RS-232C, RS-422 communication: 0
For RS-485 communication: Change depending on environment
Beginning code STX Invalid
Terminating resistance CR
Modem initialization No initialization
Setting Items Contents Remarks
Signal line change 3W Set all switches to 3W.
Setting Item Contents Remarks
Signal level change RS-485
Turn on all three switches of the CH
for connection.
Terminating
resistance setting
ON at termination
3Wire
5Wire
1
2
O
N
RS-485
RS-422
O
N
RS-485
RS-422
OFF
ON