15-20 15. Panasonic
PLC
Make PLC settings using the programming tool “FPWIN GR7”.
For more information, refer to the PLC manual issued by the manufacturer.
FP7 configuration
Calendar
This model is equipped with a calendar function; however, the calendar data cannot be written from the V series. Thus, time
correction must be performed on the PLC side.
Available Device Memory
The available setting range of device memory varies depending on the PLC model. Be sure to set within the range available for
the PLC to be used. Use [TYPE] when assigning indirect device memory for macro programs.
Setting Item Setting
Built-in
ET-LAN
Basic information
on communication
Local IP address Set the IP address of the PLC.
Subnet mask Set the subnet mask of the PLC.
Default gateway Set the default gateway of the PLC.
User connection
information
settings
Operation mode MEWTOCOL-7
Connection usage Use
Open system
(server/client)
Server connection (target station as desired) / server connection
(target station specified)
Open system
(automatic/manual)
Open automatically
Communication mode UDP/IP / TCP/IP
Local port No. Set the port number of the PLC (8000 to 65535).
Target por t No.
Port number of the V9
(communication mode: TCP/IP, open system (server/client):
Not required for server connection (target station as desired))
Unused connection time 0
Target por t set t ing method Specify the IP address (IPv4).
Target IP address
IP address of the V9
(communication mode: TCP/IP, open system (server/client):
Not required for server connection (target station as desired))
Device Memory TYPE Remarks
DT (data register) 00H *1
X (external input) 01H
WX as word device; X0 to X1F and X70 to X9F: read only
*1
Y (external output) 02H
WY as word device; Y0 to Y9, Y13, Y15 to Y1F, Y70 to Y9F: read only
*1
R (internal relay) 03H
WR as word device, including special relays
*1
L (link relay) 04H
WL as word device
*1
LD (link register) 05H *1
T (timer/contact) 09H
Read only
*1
C (counter/contact) 0AH
Read only
*1
P (pulse relay) 0BH
Read only
*1
E (error report relay) 0CH Read only
SD (system data) 0DH Read only
SR (system relay) 0EH WS as word device, read only
IN (direct input) 0FH
WI as word device, read only
*2
OT (direct output) 10H
WO as word device
*2
UM (unit memory) 11H *2
TS (timer/set value) 12H
Double-word
*1
TE (timer/elapsed value) 13H
Double-word
*1
CS (counter/set value) 14H
Double-word
*1
CE (counter/elapsed value) 15H
Double-word
*1
I (index register) 16H Double-word