3-11
Section 3 System Denition
3-3-5 Digital lter setting
You can set the digital lter for inputs of the main unit. This item is set in units of two points for the input terminals X0 to X15 and
in units of four points for the input terminals X16 to X35.
Select any of the following: “Not set (uncheck)”, “0.5 micro s,” “1 micro s,” “1.5 micro s,” “2 micro s,” “2.5 micro s,” “3 micro s,” “3.5
micro s,” “10 micro s,” “30 micro s,” “100 micro s,” “300 micro s,” “1 ms,” “3 ms,” “3/10 ms,” “10 ms,” or “15 ms”
* By default, “1.5 micro s” (“OFF to ON: 1.5 µs, ON to OFF: 1.5 µs”) is selected.
<Setting procedure>
Click the [DI Filter Denition] tab on the “Main unit parameter” dialog box to display the following window.
Set the digital lter, and then click the [OK] button.
Uncheck the box not to set the digital lter.