1-61
Section 1 Specications
1-9 Calendar Function
The values of the calendar built in a main unit of the MICREX-SX series SPF can be monitored and set from D300win. They can
also be monitored and set from an application program.
1-9-1 Calendar value range
The calendar can measure calendar values from 1970-01-01 00:00:00 through 2069-12-31 23:59:59.
Notes:
One second after 2069-12-31 23:59:59, the date and time will turn back to 1970-01-01 00:00:00.
1-9-2 Calendar accuracy
The accuracy of the calendar (clock) in a main unit is ±20 seconds per day (at an ambient temperature of 25°C, when active).
Notes:
The accuracy of the calendar varies depending on the environmental conditions such as an ambient temperature.
When a main unit is to be used in a system where a high calendar accuracy is required, measure the actual calendar accuracy
and determine the inspection (clock calibration) period.
1-9-3 How to monitor and set the calendar from D300win
1) Click the [Project Control] button in the menu bar. The “Control” dialog box opens.
2) Click the [Calendar/Watch] button to display the current value.
Click here.
Click here.
Click this button.
After setting values, click this button.
Set values
Current values for
date and time
3) Click the [Change ...] button. The “PLC time setting” dialog box opens. On this dialog box, you can set any desired value.