Address Name Description Level
%MX10.38.0 Application WDT error
ON when the execution time of a default task exceeds the
preset value of a watchdog timer.
Fatal fault
%MX10.38.1 Application execution error
ON when an error occurs during user program execution that
causes “temporary size-over.”
Fatal fault
%MX10.38.2
|
%MX10.38.10
Not used
%MX10.38.11 FB instance setup error ON when the specied storage address is not found. Fatal fault
%MX10.38.12 Initial value setup error
ON when the set initial value exceeds the dened range of a
storage area.
Fatal fault
%MX10.38.13 SFM boundary denition error
ON when the set size exceeds the capacity of the system FB
instance memory (SFM).
Fatal fault
%MX10.38.14 POU instruction error ON when there is an error in the POU. Fatal fault
%MX10.38.15 Task registration error ON when there is an error in the task registration. Fatal fault
%MX10.39.0 Missing level 0 task
ON when a task is missing.
These bits can be set OFF by an application program.
Nonfatal fault
%MX10.39.1 Missing level 1 task
%MX10.39.2 Missing level 2 task
%MX10.39.3 Missing level 3 task
%MX10.39.4 Level 0 task slow-down
ON when program execution is deferred and the predened
xed cycle time is not Maintained.
These bits can be set OFF by an application program.
Nonfatal fault
%MX10.39.5 Level 1 task slow-down
%MX10.39.6 Level 2 task slow-down
%MX10.39.7 Level 3 task slow-down
%MX10.39.8
|
%MX10.40.3
Not used
%MX10.40.4 Missing level 4 task
ON when a task is missing.
These bits can be set OFF by an application program.
Nonfatal fault
%MX10.40.5 Missing level 10 task
%MX10.40.6 Missing level 11 task
%MX10.40.7 Missing level 12 task
%MX10.40.8 Missing level 13 task
%MX10.40.9 Missing level 14 task
%MX10.40.10 Missing level 15 task
%MX10.40.11 Missing level 16 task
%MX10.40.12 Missing level 17 task
%MX10.40.13 Missing level 18 task
%MX10.40.14 Missing level 19 task
%MX10.40.15 Not used
%MX10.41.0
|
%MX10.41.3
Not used
(12) Application program error factor %MW10.38 to %MW10.41