EasyManua.ls Logo

Fuji Electric SPH Series - Writing;Reading Data To;From Memory Pack

Fuji Electric SPH Series
151 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1-63
Section 1 Specications
1-10 Writing/Reading Data to/from Memory Pack
You can write/read data of the data memory (standard memory and retain memory) to/from a memory pack (Type: NA8PMF-20)
that is mounted on a main unit.
A memory pack has three areas for writing data.
(The size of the data storage area 1 and 2 is 4K words each, and the size of the data storage area 3 is 8K words.)
Use the parameters assigned to the special registers to issue a write/read command.
Memory pack
(NA8PMF-20)
Reading
Writing (Note)
Data memory
• Standard memory (M)
• Retain memory (M)
Special register
(Parameter)
Write/Read command
Data storage area 1
(4K Words)
Data storage area 2
(4K Words)
Data storage area 3
(8K Words)
Notes:
Even if the protect switch of the memory pack is set to on, data can be written in the memory pack.
<Special register>
Address Name Description
%MW3.61440
Parameter for data storage
area 1 of memory pack
Data memory type (1: Standard memory, 3: Retain memory)
%MW3.61441
• Data memory start address of data to be written
• Data memory start address to store read data
%MW3.61442 Number of words to write/read (Note 1)
%MW3.61443
Request command
%MW3.61444
Operation status
%MW3.61445 Actual number of written/read words
%MW3.61448
|
%MW3.61453
Parameter for data storage
area 2 of memory pack
Same as “Parameter for data storage area 1”
%MW3.61456
|
%MW3.61461
Parameter for data storage
area 3 of memory pack
Same as “Parameter for data storage area 1”
15 14 0
Request type
5754h: Write request
5244h: Read request
Request bit
1: Request issued, 2: No request
f
Bit address
15 14 13 12 11 8 7 0
Error code
Executing
f
Bit address
Abnormal end
Normal end (Note 2)

Table of Contents